📈 Heating Load Density
<15Good
15–25Average
25–40Poor
40–60Very Poor
>60
⚙ Equipment Sizing Recommendations
Room-by-Room Load Summary
| # | Room | Area | Heating BTU/hr | Cooling BTU/hr | Heat % | Cool % |
|---|
How to Calculate Whole-House HVAC Loads
Start with the project name, city, and design temperatures. Use the design temperature lookup for ASHRAE 99% heating and 1% cooling temperatures for your city. The ΔT values auto-calculate.
Enter average wall R-value, window U-factor, window percentage, infiltration ACH, and mechanical ventilation rate. These are used to calculate the system-level loads beyond individual rooms. The U-value calculator helps determine effective R-values for your wall assemblies.
Add each conditioned room with its floor area and pre-calculated heating and cooling loads. Use the Room Load Calculator for each room first, or the Heating & Cooling Load Estimator to calculate all rooms at once. You can also use the "Load Typical House" button to pre-fill a sample 2,000 ft² two-storey home.
Click Calculate Whole-House Load for an instant summary showing total loads, load density rating, equipment size recommendations per standard 1.4×/1.15× sizing rules, room-by-room table, and two pie charts showing heating and cooling load sources.
Export the complete PDF report for permit submission. Then use the recommended equipment size to select your system with the furnace sizing calculator, heat pump sizing calculator, or AC sizing calculator. Then design the duct system with the duct sizing calculator.
Whole-House HVAC Load Calculations
The whole-house HVAC load is the total rate of heat that must be added (heating) or removed (cooling) from a home to maintain design indoor temperatures. It is the sum of all room loads plus system-level loads — infiltration, mechanical ventilation, and humidification — and directly determines what size furnace, air conditioner, or heat pump to install.
Room Loads vs. Whole-House Load
Individual room loads (from the room load calculator or load estimator) are used to size supply ducts and registers. The whole-house load is the sum of all rooms plus shared system loads and is used to select the central HVAC equipment. Note that the whole-house load may be slightly less than the arithmetic sum of all peak room loads due to load diversity — not all rooms peak simultaneously.
Load Density — The Key Performance Indicator
Load density (BTU/hr per square foot) reveals how energy-efficient a building is. Modern Canadian homes built to NBC 2015+ standards achieve 20–28 BTU/hr·ft² heating. Homes from the 1980s-1990s typically fall in the 30–45 BTU/hr·ft² range. Pre-1980 homes with little insulation can exceed 60 BTU/hr·ft². Net-zero homes target below 15 BTU/hr·ft². Use the load comparison tool to see how much improvement insulation upgrades, window replacement, or air sealing could achieve.
Standard Equipment Sizing Rules
Per standard residential sizing practice, heating equipment may be sized up to 1.4× the calculated heating load to accommodate standard increments. Cooling equipment should not exceed 1.15× the sensible cooling load to prevent short-cycling. The furnace sizing calculator, heat pump sizing calculator, and AC sizing calculator each apply these rules automatically.
After Whole-House Loads — Next Steps
- Select heating equipment: Furnace Sizing, Heat Pump Sizing, Boiler Output
- Select cooling equipment: AC Sizing, Mini-Split Sizing
- Design the duct system: Duct Sizing, CFM Calculator
- Verify ventilation: Ventilation Rate Calculator
- Evaluate energy savings: Payback Period Calculator
- Check compliance: ASHRAE 62.1 Calculator
Frequently Asked Questions
It depends heavily on climate and insulation. For a 2000 ft² two-storey home in Toronto (cold climate, average insulation): expect approximately 60,000–80,000 BTU/hr heating and 24,000–36,000 BTU/hr cooling. In Edmonton (very cold), heating could reach 80,000–100,000 BTU/hr. In Vancouver (mild), it may only be 35,000–50,000 BTU/hr. A well-insulated 2015+ code home in Toronto might achieve 45,000–60,000 BTU/hr. Always calculate from actual building data using this tool or the Heat Load Calculator.
The furnace output BTU/hr must equal or exceed the whole-house heating load. Standard sizing practice allows up to 1.4× the load to accommodate standard equipment sizes. For a 70,000 BTU/hr heating load, a furnace with 70,000–98,000 BTU/hr output is acceptable. Note that furnace input capacity is higher than output — divide output by AFUE efficiency to get input. A 95% AFUE furnace with 80,000 BTU/hr output requires ~84,000 BTU/hr input capacity. Use the Furnace Sizing Calculator for the complete calculation.
Yes. The whole-house heating load from this calculator is the key input for heat pump sizing. For a heat pump, you must verify that the selected unit achieves rated capacity at the outdoor design temperature (heat pumps lose capacity in very cold weather). In Canadian climates below -15°C, cold-climate heat pumps (HSPF rated at -15°C or lower) are needed. The heat pump sizing calculator handles this analysis with temperature-derated capacity curves.
Oversized equipment is one of the most common problems in residential HVAC. Many contractors size by square footage rules of thumb, resulting in 1.5–2× oversized equipment. This causes short-cycling (the system runs in short bursts instead of sustained operation), poor dehumidification in summer, temperature swings, and reduced equipment life. If your calculated load is significantly lower than your installed equipment, it may be worth having a proper load calculation done and considering right-sizing at the next replacement.
Related HVAC Tools
Component-level heating load
Individual room analysis
Full load calculation report
Size from whole-house load
Cold-climate heat pump
Friction-rate-based duct design
ROI on efficiency upgrades
Before vs. after retrofits