🧦 Thermal Resistance Calculator

U-Value / R-Value Calculator

Calculate the effective R-value and U-factor of any multi-layer wall, roof, or floor assembly. Add insulation layers, sheathing, framing, air films, and finishes. Includes framing correction for wood-framed construction. Essential input for all heat load calculations.

Unit System:
💡
Add layers from outside to inside. Include surface air films (exterior: R-0.17, interior: R-0.68 imperial). R-values add in series. Use the framing correction to account for thermal bridging through wood studs.
Layer Description Thickness (in) R-Value (hr·ft²·°F/BTU) Material
×
ft²
°F
💡 Q = U × A × ΔT gives heat loss in BTU/hr. Use with Heat Load Calculator.
🧦 Assembly R-Value & U-Factor Results

Assembly Cross-Section Visualization

Layer-by-Layer Breakdown

#LayerThicknessR-ValueR-Value (SI)% of Total

Compare to Building Code Benchmarks

Export:

Common Material R-Values Reference

MaterialR-Value per inch (Imperial)RSI per 25mm (Metric)Notes
Fiberglass batt (standard)R-3.1 to R-3.4/inRSI 0.54–0.59/25mm2×4: R-11–13; 2×6: R-19–21
Fiberglass batt (high-density)R-3.7 to R-4.3/inRSI 0.64–0.75/25mm2×6: R-21–25; 2×8: R-30
Mineral wool / Rockwool battR-3.7 to R-4.2/inRSI 0.64–0.73/25mmBetter fire & moisture resistance
Blown cellulose (attic)R-3.2 to R-3.8/inRSI 0.55–0.66/25mmSettles ~20% over time
Blown fiberglass (attic)R-2.2 to R-2.7/inRSI 0.38–0.47/25mmLess settling than cellulose
Spray polyurethane foam (closed-cell)R-6.0 to R-6.5/inRSI 1.04–1.13/25mmAir barrier; moisture barrier
Spray polyurethane foam (open-cell)R-3.5 to R-3.8/inRSI 0.61–0.66/25mmAir barrier; vapour permeable
EPS rigid foam (Type II)R-3.6 to R-4.0/inRSI 0.63–0.70/25mmCommon for continuous insulation
XPS rigid foam (extruded)R-5.0/inRSI 0.87/25mmExcellent moisture resistance
Polyisocyanurate (polyiso)R-6.0 to R-6.5/inRSI 1.04–1.13/25mmBest R/inch; loses value in cold
OSB sheathing (½″)R-0.5 totalRSI 0.09Structural; low R-value
Plywood sheathing (½″)R-0.6 totalRSI 0.10
½″ Drywall / GypsumR-0.45 totalRSI 0.08
Wood siding (½″)R-0.80 totalRSI 0.14
Brick veneer (4″)R-0.44 totalRSI 0.08Thermal mass, not insulation
Exterior air filmR-0.17 totalRSI 0.030ASHRAE standard condition
Interior air film (horizontal)R-0.68 totalRSI 0.120Heat flow upward (winter ceiling)
Interior air film (vertical)R-0.68 totalRSI 0.120Walls
2×4 Douglas Fir stud (3.5″)R-4.4 totalRSI 0.77Used in parallel path calc
2×6 Douglas Fir stud (5.5″)R-6.9 totalRSI 1.22

Understanding R-Value and U-Value in HVAC

R-value and U-value are the two most important thermal performance metrics in HVAC and building science. Understanding the difference between them — and how to calculate assembly values from individual material layers — is essential for accurate heat load calculations, equipment sizing, and energy code compliance.

R-Value vs. U-Value: The Key Relationship

R-value (thermal resistance) measures how well a material resists heat flow. It is expressed in hr·ft²·°F/BTU (Imperial) or m²·K/W (Metric, called RSI). Higher R-value = better insulation. R-values are additive for layers in series: R_total = R₁ + R₂ + R₃ + ... This is why you simply add up all the layers of a wall assembly.

U-value (thermal transmittance, also called U-factor) measures the rate of heat transfer through a material. It is expressed in BTU/hr·ft²·°F or W/m²·K. Lower U-value = better insulation. U-value is the reciprocal of total R-value: U = 1/R_total. The heat loss formula uses U-value: Q = U × A × ΔT, where Q is heat loss in BTU/hr, A is surface area in ft², and ΔT is the indoor-outdoor temperature difference in °F. This is the fundamental formula in the heat load calculator.

Why Framing Correction Matters

A 2×6 wall with R-20 fiberglass batts does NOT have an effective R-value of 20. Wood studs, plates, and headers conduct heat much better than insulation — typically R-1.25/inch vs. R-3.5+/inch for fiberglass. In a typical 2×6 wall at 16″ o.c., framing occupies about 15-17% of the wall area. Applying the parallel path calculation, the effective R-value of the cavity is reduced by a framing correction factor of approximately 0.83 — so R-20 batts in 2×6 framing yield about R-16.6 in the cavity zone, not R-20. Add the other layers (sheathing, drywall, air films) and you might get R-18 to R-19 overall. This is why the heat load calculator asks for effective R-value, not nominal insulation R-value.

Continuous Insulation (CI) and Its Impact

Continuous insulation (CI) applied to the exterior of a wall (rigid foam, mineral wool batts, or spray foam) bypasses the framing entirely and is not subject to the framing correction factor. This is why adding even R-5 of exterior CI to a 2×6 wall can improve effective R-value more than upgrading from R-20 to R-24 batts inside. When entering CI in the layer list, mark it as non-framed to exclude it from the correction.

NBC Canada R-Value Requirements

National Building Code (NBC) Canada requires minimum effective RSI (SI R-value) for building envelopes by climate zone. The NBC Canada compliance guide has the full zone map and requirements. Use this calculator to verify your assembly meets or exceeds the required effective RSI before entering it into load calculations.

Frequently Asked Questions

Yes — R-values of layers in series add directly. This is one of the most useful properties of R-value and why it is preferred for assembly calculations. If your wall has exterior air film (R-0.17) + OSB sheathing (R-0.5) + R-20 insulation + drywall (R-0.45) + interior air film (R-0.68), the total is R-21.8 before framing correction. U-values do NOT add — always convert to R, sum, then convert back to U.

Nominal R-value is the rated R-value of the insulation product alone (e.g., "R-20 batt"). Effective R-value is the actual thermal performance of the entire wall assembly including framing correction, all other layers, and surface air films. Effective R-value is always lower than nominal due to thermal bridging through framing. For example, R-20 batts in 2×6 framing yield approximately R-18–19 effective total assembly value. Always use effective R-value in heat load calculations.

Multiply Imperial R-value by 0.176110 to get RSI (m²·K/W). Divide RSI by 0.176110 to get Imperial R-value. For example: R-20 imperial = 20 × 0.176110 = RSI 3.52. Our unit converter handles this conversion, and this calculator displays both automatically. Note: RSI is also called R-value (SI) or metric R-value in Canadian building codes.

Yes, for calculating heat loss (U × A × ΔT), you should include surface air films in the total R-value because they are a real resistance to heat flow. ASHRAE standard surface film resistances are: exterior (winter, 15 mph wind): R-0.17 imperial (RSI 0.030); interior (still air, vertical surface): R-0.68 (RSI 0.120); interior (still air, horizontal, heat flow upward): R-0.61 (RSI 0.107). This calculator includes air films in its presets and the "Add Air Films" button adds them automatically.