Sensible Heat Ratio (SHR)
Heat Gain by Component
Detailed Results Table
| Component | Sensible (BTU/hr) | Latent (BTU/hr) | Total (BTU/hr) | % of Total |
|---|
How to Use the Cooling Load Calculator
Use the ASHRAE 1% summer dry-bulb and coincident wet-bulb design temperatures for your city. The design temperature lookup provides these values. For the wet-bulb, use our wet-bulb calculator if only dry-bulb and RH are known.
This calculator separates windows by orientation because solar heat gain peaks at different times: east windows peak in the morning, west in the afternoon, south at midday. Enter area and SHGC for each orientation. Use a lower SHGC (0.20–0.25) for south and west glazing to minimize cooling loads.
Internal gains are often the largest cooling load component in commercial buildings. For residential, lighting and equipment at 1.0–1.5 W/ft² total is typical. For commercial offices, use 0.8 W/ft² lighting + 1.5–2.0 W/ft² equipment. Each occupant adds both sensible and latent heat — select the appropriate activity level.
The SHR indicates what fraction of your total cooling load is sensible vs. latent. A low SHR (below 0.75) means significant dehumidification is needed — you must select equipment with a low SHR rating. Most standard AC equipment has SHR around 0.75–0.80. For a more detailed analysis, see the SHR calculator and dew point calculator.
Use the total cooling load to size your AC system with the AC sizing calculator or mini-split sizing calculator. For commercial projects, also run the heat load calculator to compare and size for both seasons.
HVAC Cooling Load Calculations — Complete Guide
A cooling load calculation determines the peak rate of heat gain a building experiences during summer, measured in BTU/hr or kW. Unlike heating load (which is primarily conduction-driven), cooling loads involve multiple simultaneous heat sources that peak at different times of day, making the calculation considerably more complex.
The Six Sources of Cooling Load
This calculator accounts for all six recognized sources of cooling heat gain per ASHRAE fundamentals:
- Solar heat gain through windows: The dominant cooling load component in most buildings. Use low-SHGC glazing and external shading to reduce it. The solar heat gain calculator provides detailed orientation analysis.
- Conduction through walls and roof: Driven by the outdoor-indoor temperature difference, wall color (solar absorptance), and U-value. Dark roofs are a major contributor — cool roofs can reduce this by 50–70%.
- Internal gains from occupants: Each person produces sensible body heat (raising air temperature) and latent heat (moisture). Activity level matters — a gym occupant generates 3× more latent heat than a seated office worker.
- Lighting and equipment: All electrical energy consumed inside the conditioned space eventually becomes heat. LED lighting has reduced this significantly vs. fluorescent, but computing equipment loads continue to grow.
- Ventilation — outdoor air: Hot humid summer air brought in for ventilation must be cooled and dehumidified. This adds both sensible and latent load, partially recoverable with an ERV.
- Infiltration: Uncontrolled air leakage adds sensible and latent load proportional to the humidity difference between indoors and outdoors.
Sensible vs. Latent Cooling — Why It Matters for Equipment Selection
Sensible cooling lowers air temperature. Latent cooling removes moisture (dehumidification). The Sensible Heat Ratio (SHR) is the fraction of total cooling that is sensible. Most standard residential AC equipment is rated at SHR 0.75–0.80. If your space has a very low SHR (below 0.70) — due to high occupancy, cooking, or humid climate — you need equipment with a matching low SHR or a dedicated dehumidifier. The psychrometric calculator and dew point calculator help analyze moisture conditions in detail.
Peak vs. Average Cooling Loads
Cooling loads fluctuate throughout the day. West-facing windows peak in the late afternoon. East-facing windows peak in the morning. Internal gains from people and lighting peak during occupancy hours. This calculator uses simultaneous peak assumptions — a conservative approach suitable for equipment sizing. For energy analysis (annual energy use), proceed to the energy savings estimator which uses hourly profiles.
Next Steps After Your Cooling Load
- Size your AC: AC Sizing Calculator or Mini-Split Sizing Calculator
- Compare with heating: Heat Load Calculator and Heat Pump Sizing
- Design air distribution: CFM Calculator and Duct Sizing Calculator
- Analyze moisture: Psychrometric Calculator and Dew Point Calculator
- Evaluate energy: SEER Calculator and Payback Period Calculator
Frequently Asked Questions
Heat gain is the total rate of heat entering a space. Cooling load is the rate at which the HVAC system must remove heat. They differ because buildings have thermal mass that stores heat — so the actual cooling load lags behind the instantaneous heat gain. This calculator uses the simplified simultaneous peak approach (conservative for equipment sizing). ASHRAE's Radiant Time Series method is more precise for design.
SHGC (Solar Heat Gain Coefficient) is the fraction of solar energy that passes through a window as heat gain. For cooling load reduction: south and west windows should have SHGC ≤ 0.25. North windows have minimal solar gain so SHGC matters less. East windows benefit from low SHGC in hot climates. Energy Star requires SHGC ≤ 0.40 for most Canadian climate zones. High-performance triple-pane windows can achieve SHGC of 0.15–0.20. The solar gain calculator analyzes this in detail by month.
The most impactful measures in order of typical savings: (1) External window shading — overhangs, awnings, exterior blinds (20–40% reduction in solar gain). (2) Low-SHGC glazing (15–30% reduction). (3) Cool roof coating (10–20% reduction in roof heat gain). (4) Increased ceiling/roof insulation (5–15% reduction). (5) LED lighting to replace fluorescent (5–10% internal gain reduction). (6) ERV to pre-cool ventilation air (5–15% ventilation load reduction). Use the load comparison tool to quantify savings before and after improvements.
Yes, this is very common in Canada. A well-insulated home in Toronto may have a heating load of 60,000 BTU/hr but only 24,000 BTU/hr of cooling load — a 2.5:1 ratio. The heating load is driven by a large temperature differential (up to 50°C ΔT in winter) while the summer cooling differential is much smaller. This is why many Canadian homes are adequately served by 2-ton AC systems despite requiring 80,000+ BTU furnaces. When selecting a heat pump, always size for the larger (heating) load.
Related HVAC Tools
Full heating load analysis
Quick BTU estimate
Window solar heat gain
Size from cooling load
Enthalpy & humidity
Moisture analysis
Airflow from cooling load
Efficiency rating