💧 Unit Converters

Fluid Flow Rate Converter

Convert between GPM, L/min, L/s, m³/h, m³/s, and US gal/hr instantly. Includes a heat-to-flow calculator for hydronic sizing, plus chilled water, heating hot water, and cooling tower flow rate reference tables.

US gallons / minute
litres / minute
litres / second
cubic metres / hour
cubic metres / second
US gallons / hour

For glycol systems, change Cp: 30% EG = 3.60, 50% EG = 3.30 kJ/kg·K. Use the Specific Heat Converter for Cp reference values.

💧 Conversion Results
US GPM
--
gal/min
L/min
--
litres/min
L/s
--
litres/sec
m³/h
--
m³/hour
m³/s
--
m³/second
gal/hr
--
US gal/hour

Key Conversion Factors

1 GPM    = 3.78541 L/min = 0.06309 L/s = 0.22712 m³/h
1 L/min  = 0.26417 GPM = 0.01667 L/s = 0.06000 m³/h
1 L/s    = 15.8503 GPM = 60 L/min = 3.6 m³/h
1 m³/h   = 4.40287 GPM = 16.667 L/min = 0.27778 L/s
Flow (L/s) = Q (kW) / (Cp (kJ/kg·K) x ΔT (°C)) for water: ÷ 4.187 x ΔT

Hydronic Heating Flow Rate Reference (Water, ΔT = 10°C)

Heat Load (kW)L/sL/minGPMTypical Application
50.127.21.9Single zone / small radiant loop
100.2414.33.8Small zone / one-pipe baseboard
200.4828.77.6Residential boiler system (small home)
350.8450.313.3Residential boiler (typical Canadian home)
501.1971.718.9Large home or small commercial
1002.3914337.9Commercial heating coil or small AHU
2004.7828775.7Medium commercial / institutional heating
50011.95717189Large commercial heating plant
100023.91434379District heating main or large plant

Chilled Water Flow Rate Reference (Water, ΔT = 6°C)

Cooling Load (kW)TonsL/sL/minGPM
35101.3983.622.1
70202.7916744.1
175506.97418110
35110013.9836221
52715021.01258332
70320027.91675443
105530041.92513664
175850069.841881107
3517100014083762213

Flow rates based on water at 6°C delta-T (typical Canadian chilled water design). Higher delta-T (8-12°C) reduces flow and pump energy. For glycol systems, adjust using the Specific Heat Converter to find the correct Cp.

Export:

How to Use the Flow Rate Converter

1
Convert Any Flow Rate Unit

Type a flow rate in GPM, L/min, L/s, m³/h, m³/s, or US gal/hr. All other units update instantly. Use the quick presets for common HVAC flow rates: residential circulator (7.6 GPM), 100-ton chiller (222 GPM), or cooling tower (1000 m³/h).

2
Calculate Flow from Heat Load

Enter heat load in kW, temperature differential in °C, and fluid Cp in kJ/kg·K in the Heat Load to Flow Rate Calculator. For water use Cp = 4.187. For 30% ethylene glycol use 3.60, and for 50% glycol use 3.30. Results show flow in all major units and populate the main converter automatically.

3
Read the Context Band

The result panel identifies what HVAC system your flow rate corresponds to: residential circulator, small commercial, chilled water main, or large central plant. This helps confirm a calculated flow is in the right range before selecting pumps or sizing pipes.

4
Cross-Reference the Tables

Two reference tables cover heating hot water flow at 10°C delta-T (1 kW to 1000 kW) and chilled water flow at 6°C delta-T (10 tons to 1000 tons). Use these to quickly identify the required flow for any load without manual calculation, then feed the result into pump selection and pipe sizing tools.

Fluid Flow Rate in HVAC -- Complete Guide

Fluid flow rate determines pipe sizing, pump selection, heat exchanger performance, and system pressure drop in every hydronic HVAC system. Canadian HVAC engineering uses L/s and m³/h; US pump and equipment ratings use GPM. Converting fluently between these units, and calculating flow from heat load, is a daily requirement in hydronic heating and chilled water design.

GPM to L/s -- The Core Conversion

The most common conversion in Canadian hydronic work is between US GPM and L/s. The factor: 1 GPM = 0.06309 L/s, or 1 L/s = 15.850 GPM. A circulator pump rated at 10 GPM delivers 0.631 L/s. A chiller rated for a 222 GPM flow delivers 14.0 L/s. GPM also converts to L/min by multiplying by 3.785 -- a quick field approximation is 1 GPM ≈ 3.8 L/min. For European equipment ratings in m³/h: 1 GPM = 0.227 m³/h, or 1 m³/h = 4.40 GPM.

Calculating Flow from Heat Load

The fundamental hydronic equation is Q = ṁ x Cp x DeltaT, rearranged for flow: ṁ (kg/s) = Q (kW) / (Cp (kJ/kg·K) x DeltaT (K)). For water (Cp = 4.187 kJ/kg·K, density ≈ 1 kg/L at typical operating temperatures): flow (L/s) = Q (kW) / (4.187 x DeltaT). A 50 kW load at 10°C DeltaT needs 50 / (4.187 x 10) = 1.19 L/s = 71.5 L/min = 18.9 GPM. For glycol systems, use the lower Cp from the Specific Heat Converter -- 30% ethylene glycol has Cp = 3.60 kJ/kg·K, so the same 50 kW load at 10°C DeltaT requires 50 / (3.60 x 10) = 1.39 L/s -- 17% more flow than water.

Delta-T and System Efficiency

A higher temperature differential (delta-T) between supply and return reduces the required flow rate for the same heat transfer. Conventional Canadian hot water heating systems design for 10°C DeltaT (80°C supply / 70°C return). Modern condensing boiler systems use lower water temperatures with higher DeltaT of 15-20°C, reducing flow rate by 33-50% compared to conventional systems. Lower flow means smaller pipes, smaller pumps, lower pump energy, and reduced capital cost. Chilled water systems typically use 6°C DeltaT in Canada (7°C supply / 13°C return), though designers increasingly push to 8-10°C DeltaT to reduce pump energy in variable flow systems.

Pipe Velocity and Flow Rate

Once you have the required flow rate, pipe diameter is sized to keep velocity within acceptable limits. For hydronic systems, typical design velocities are 0.9 to 1.8 m/s for mains (3 to 6 ft/s) and 0.6 to 1.2 m/s for branches (2 to 4 ft/s). Velocity (m/s) = flow (m³/s) / pipe area (m²). For a 2-inch nominal copper pipe (ID approximately 50.8 mm, area = pi x 0.0254² = 0.002027 m²): at 1.0 L/s (0.001 m³/s), velocity = 0.001 / 0.002027 = 0.493 m/s -- well within limits. Use the Air Velocity Converter for velocity conversions and the Area Converter for pipe cross-section areas.

Frequently Asked Questions

Multiply US GPM by 3.78541 to get L/min. So 1 GPM = 3.785 L/min, 10 GPM = 37.85 L/min, and 100 GPM = 378.5 L/min. To go the other way, divide by 3.78541. A quick approximation: 1 GPM ≈ 3.8 L/min. Note that this is US gallons per minute -- if working with Imperial gallons, multiply by 4.546 instead. Most North American pump curves use US GPM.

Flow (L/s) = heat load (kW) / (Cp x DeltaT). For water (Cp = 4.187 kJ/kg·K): flow = kW / (4.187 x DeltaT°C). A 35 kW boiler at 10°C DeltaT needs 35 / (4.187 x 10) = 0.836 L/s = 50.2 L/min = 13.3 GPM. For glycol: use Cp = 3.60 (30% EG) or 3.30 (50% EG). Use the Heat Load to Flow Rate Calculator above -- it handles the math and shows all flow unit equivalents at once.

At a 6°C delta-T (7/13°C supply/return, common in Canadian chilled water design): flow (L/s) = cooling kW / (4.187 x 6) = cooling kW / 25.1. A 100-ton (351.7 kW) chiller needs 351.7 / 25.1 = 14.0 L/s = 221 GPM. A 50-ton chiller needs 7.0 L/s = 111 GPM. Increasing DeltaT to 8°C reduces flow by 25%, lowering pump energy significantly. The chilled water flow reference table above covers 10 to 1000 tons.

A typical Canadian home with 20 kW heating load at 10°C DeltaT needs: flow = 20 / (4.187 x 10) = 0.478 L/s = 28.7 L/min = 7.6 GPM. At 20°C DeltaT (condensing boiler design): 0.239 L/s = 14.3 L/min = 3.8 GPM -- half the flow, smaller pipes, lower pump energy. Enter your home's heat load and DeltaT in the calculator above to get the exact flow rate for your system.