🌡 Heat Rejection

Condenser Sizing Calculator

Calculate heat of rejection and required condenser capacity for air-cooled and water-cooled systems. Find condensing temperature, approach temperature, and minimum condenser size from your cooling load and operating conditions. Covers R-410A, R-32, R-454B, R-22, and R-404A. Pair with the compressor sizing calculator for complete system design.

BTU/hr
1 ton = 12,000 BTU/hr
COP
°F
°F
°F
🌡 Condenser Sizing Results
ParameterValueNote
Export:

Condenser sizing for Canadian HVAC systems

The condenser must reject all the heat the refrigeration system absorbs — that's the cooling load plus the compressor heat input. This total is called the heat of rejection. For a system with a COP of 3.0, the compressor adds 33% of the cooling load as heat, so the condenser must reject 133% of the cooling load. At COP 2.5, that rises to 140%. Getting this number right is critical because an undersized condenser drives up condensing temperature, which increases compressor power draw, reduces system capacity, and can cause high-pressure lockout on hot summer days.

In Canada, the peak summer outdoor design temperature varies significantly by city. Toronto uses 31°C (88°F), Calgary uses 29°C (84°F), and Vancouver uses 27°C (81°F) for ASHRAE 1% design conditions. Always design the condenser to reject full heat of rejection at the local 1% design temperature, not a national average. A condenser sized for Calgary will be undersized for a Toronto installation at the same cooling load.

Approach temperature and its impact on system efficiency

Approach temperature is the difference between condensing temperature and entering air (or water) temperature. A smaller approach means a larger, more efficient condenser. A 15°F approach at 95°F outdoor ambient gives a 110°F condensing temperature. A 30°F approach gives 125°F. That 15°F difference in condensing temperature can cost 10-15% in system COP. For high-efficiency systems and heat pumps where seasonal performance matters, a smaller approach temperature is worth the larger condenser cost.

For air-cooled condensers, the approach also depends on airflow distribution and coil fouling. A condenser that starts the season with a 20°F approach can degrade to 30°F or more as the coil accumulates dirt and debris. Canadian systems near cottonwood trees or grain operations are especially prone to coil fouling. Design with a clean approach of 20°F but account for a fouled approach of 30°F in worst-case pressure calculations. The heat of rejection calculator gives you the full thermal load for selection.

Water-cooled condensers in Canadian commercial buildings

Water-cooled condensers achieve much smaller approach temperatures than air-cooled units — typically 5-15°F. They also allow higher condensing temperatures to be avoided, improving COP year-round. In Canadian commercial buildings, cooling towers supply condenser water at 85°F (29°C) in summer, which allows condensing temperatures of 95-100°F — well below what an air-cooled condenser achieves on a hot day. The trade-off is the added cost and maintenance of the cooling tower, water treatment, and building permits.

For water-cooled sizing, the standard rule is 3 GPM per ton of refrigeration for the condenser water circuit. At this flow rate and a typical 10°F rise, the condenser water carries 30 BTU/hr per GPM — meaning each GPM of water removes 30 BTU/hr of heat. Use this calculator's water-cooled mode to verify your flow rate matches your heat of rejection.

Frequently Asked Questions

Condenser capacity must equal the heat of rejection: cooling load plus compressor heat input. For a system with COP 3, heat of rejection is 133% of the cooling load. To size the condenser, you need the heat of rejection and the approach temperature — difference between condensing temperature and entering air temperature. A typical air-cooled condenser has a 20-30°F approach. At 95°F outdoor ambient and 25°F approach, condensing temperature is 120°F. Always use the actual peak summer design temperature for your Canadian location from ASHRAE design data, not a national average. Use the heat of rejection calculator to confirm your total condenser load.

Approach temperature is the difference between condensing temperature and entering fluid temperature. A smaller approach means a larger, more efficient condenser. A 15°F approach at 95°F ambient gives 110°F condensing temperature. A 30°F approach gives 125°F — that 15°F difference can cost 10-15% in COP. For Canadian HVAC systems, approach is typically 15-25°F for air-cooled condensers. Coil fouling from dirt or cottonwood can increase the effective approach by 10°F or more over a season. Design for a clean approach but verify the system can handle worst-case fouled conditions without high-pressure lockout.