🔋 Expansion Valve

TXV Sizing Calculator

Calculate required TXV capacity and diagnose expansion valve faults on HVAC and refrigeration systems. Covers R-410A, R-32, R-454B, R-22, and R-404A. Pair with the superheat calculator to verify valve performance after installation or adjustment.

BTU/hr
PSIG
PSIG
Enter pressures above
°F SC
PSID
🔋 TXV Sizing Results
ParameterValueNote
Export:

TXV sizing: matching valve capacity to system load

The thermostatic expansion valve (TXV) controls refrigerant flow into the evaporator by maintaining a fixed suction superheat setpoint — typically 8-12°F at the evaporator outlet. Its capacity is determined by the pressure drop across it (condensing pressure minus evaporating pressure) and the density of the incoming liquid (affected by subcooling). A properly sized TXV feeds exactly the right amount of refrigerant to keep the evaporator fully loaded without flooding liquid back to the compressor.

Manufacturers rate TXV capacity at a standard pressure drop. For R-410A, the standard is typically 100 PSID. For R-22, it's usually 40 PSID. If your actual pressure drop is different from the rating condition, you must correct the valve capacity before comparing it to your system load. This calculator applies that correction automatically using the square-root relationship between pressure drop and flow rate.

Oversized vs. undersized TXV: different failure modes

An oversized TXV delivers too much refrigerant per unit of valve movement. The valve modulates aggressively, overshooting the superheat setpoint and then slamming shut, creating a hunting cycle — superheat swings of 10-20°F are common. The compressor sees rapidly changing suction conditions and operates inefficiently. If superheat repeatedly swings between very low and very high values at a regular interval, suspect an oversized valve before condemning the refrigerant charge.

An undersized TXV can't feed enough refrigerant at low pressure drop conditions. The evaporator runs partially starved, superheat climbs above setpoint, and system capacity drops. This is especially common on systems where a TXV sized for one refrigerant is reused during a retrofit to a different refrigerant — the new refrigerant may have different flow properties that change the effective valve capacity. Always re-verify TXV sizing during any refrigerant retrofit.

Sensing bulb location and TXV diagnosis

The sensing bulb controls TXV opening by measuring suction line temperature. It must be clamped firmly to a clean section of suction line, insulated from ambient air, at the 4 or 8 o'clock position (not the top or bottom of the pipe). A poorly mounted bulb reads ambient air temperature instead of suction line temperature, causing the valve to hunt or remain wide open. If you suspect a bulb problem, warm the bulb slightly with your hand — if superheat drops sharply, the bulb is responding correctly. Use the superheat calculator to measure actual superheat before and after any TXV adjustment or replacement.

For R-32 and R-454B systems, confirm the TXV is rated and charged for the refrigerant installed. An R-410A TXV bulb charged with R-410A will not control correctly on an R-32 system — the saturation pressure-temperature relationship is different, so the bulb charge produces incorrect valve opening at any given suction condition. Always match TXV bulb charge to the installed refrigerant.

Frequently Asked Questions

TXV sizing starts with system cooling capacity in BTU/hr, then corrects for actual pressure drop across the valve and actual subcooling. Manufacturers rate TXV capacity at a standard pressure drop — typically 100 PSID for R-410A. If your actual pressure drop is lower, the valve flows less and you need a larger valve. Select a TXV within 10-20% of system capacity — oversized valves hunt, undersized valves starve the evaporator. After installation, verify with the superheat calculator. Target 8-12°F of stable superheat at the evaporator outlet.

TXV hunting — repeated superheat swings above and below setpoint — most often means an oversized valve. Other causes include a poorly located or uninsulated sensing bulb, a worn valve seat, fluctuating evaporating pressure from a charge issue, or a bulb that has lost its charge. Check that the bulb is clamped at the 4 or 8 o'clock position on the suction line, insulated from ambient air, at least 6 inches from the evaporator outlet. Use the superheat calculator to confirm actual superheat and the subcooling calculator to rule out a charge issue before condemning the valve.