Carbon Monoxide Calculator

Calculate CO buildup from combustion appliances in enclosed spaces. Estimate time to hazardous concentrations and minimum ventilation to stay below Health Canada's 10 ppm 24-hour guideline.

Select a preset source or enter a custom emission rate. Rates are planning values, and actual rates vary by appliance age, tune, and combustion conditions.

m
m
m
ACH
ppm
hrs
🔥 Carbon Monoxide Results

Time to Key CO Thresholds

Concentration at End of Run Time vs. Thresholds

Ventilation Required to Maintain Safe Levels

Target LevelGuidelineTotal VentilationEquivalent ACH
Export:

How to Use This Calculator

1
Select a CO Source or Enter a Custom Rate

Pick a preset source like a gas range, water heater, or furnace with a heat exchanger leak. The preset emission rates are planning values, and the generator preset follows the roughly 1,500 g/hr that CPSC staff cite for a typical 5 kW generator engine. Use the custom rate for specific measured values or unusual appliances.

2
Enter Space Dimensions and Infiltration Rate

Enter the room or zone dimensions and the natural infiltration ACH. Tight new Canadian homes typically run 0.05 to 0.15 ACH. Average homes 0.2 to 0.5 ACH. Older leaky homes 0.5 to 1.0 ACH. The infiltration rate is the single biggest factor in how quickly CO accumulates.

3
Review Time to Thresholds

The results show when CO reaches Health Canada's 10 ppm (24-hr) guideline, the 25 ppm (1-hr) guideline, the CO alarm threshold of 70 ppm, the 200 ppm symptom level, and the immediately dangerous to life and health (IDLH) level of 1200 ppm.

4
Check Required Ventilation

The ventilation table shows the total fresh air supply in L/s, including natural infiltration, needed to hold steady-state CO at each guideline level. Use this to size makeup air, range hoods, or garage exhaust fans appropriately.

Carbon Monoxide in Canadian Buildings: Sources, Risks, and Ventilation

Carbon monoxide poisoning is a serious hazard in Canadian homes. Unlike most air quality issues that cause long-term harm through chronic exposure, CO can reach life-threatening concentrations in hours, or even minutes, from a single malfunctioning appliance. Understanding the buildup dynamics helps HVAC professionals size ventilation correctly and advise clients on where alarms need to go.

CO Buildup Physics

In a well-mixed space with a constant source and constant ventilation, CO concentration follows an exponential curve toward a steady-state value. The steady-state concentration equals the emission rate divided by the total ventilation flow rate, plus any background level. Without any ventilation, CO rises linearly until the source stops or the occupants leave. The time constant for the system is the room volume divided by the ventilation flow rate, identical to the time constant used in the dilution air calculator. A tightly sealed modern home with 0.05 ACH natural infiltration has a time constant of 20 hours, meaning CO from a moderate source can accumulate for many hours before approaching steady state. The calculator converts between emission rate and concentration at 1.165 mg/m3 per ppm (20 C).

Health Canada CO Guidelines

Health Canada's residential indoor air quality guideline for carbon monoxide sets a 24-hour limit of 10 ppm (11.5 mg/m3) and a 1-hour limit of 25 ppm (28.6 mg/m3). Both are averaged limits derived to keep blood carboxyhaemoglobin below 2.0%, so a brief excursion above 10 ppm is not by itself a 24-hour exceedance. The calculator compares the modelled concentration at the end of the run time against them, which is a conservative screen. Symptoms depend on both level and time: commonly cited exposure charts put a headache at around 200 ppm after 2 to 3 hours and life-threatening effects at 400 ppm after about 3 hours, and NIOSH sets the immediately dangerous to life or health level at 1200 ppm. Canadian CO alarms certified to CSA 6.19 are built to sound at 70 ppm sustained for 60 to 240 minutes, so they are not designed to trigger at the guideline levels of 10 to 25 ppm.

Furnace Heat Exchangers

A cracked heat exchanger is a serious CO source in Canadian homes because the furnace can distribute combustion gases through the supply air stream and the rest of the building. The calculator's furnace-leak preset is 500 mg/hr. In its example, a 173 m3 basement at 0.15 ACH settles near 17 ppm, above Health Canada's 24-hour limit but well below the 70 ppm alarm level, which is how a slow leak can go unnoticed until symptoms appear. Health Canada advises a professional inspection of fuel-burning appliances at least once a year. The heat exchanger crack test calculator covers crack testing of the exchanger itself, and the combustion air calculator covers makeup air sizing for combustion appliances.

Attached Garages

Attached garages are a significant CO source in Canadian winters because vehicles are often warmed up before driving. Health Canada advises keeping the door between the house and the garage closed and not idling vehicles in the garage, even with the garage door open. The calculator's vehicle preset is 2000 mg/hr, in line with the 2.4 to 5.4 g/hr that CPSC staff cite for idling mid-size cars of the late 1990s. In a sealed 72 m3 garage that preset reaches the 25 ppm level in about an hour and the 70 ppm alarm level in about 3 hours, and a cold engine emits more while its catalytic converter warms up. If there is any air pathway into the living space, such as around the entry door, through shared wall penetrations, or through ductwork, some of that CO follows it. Install CO alarms in hallways outside sleeping areas, as Health Canada advises.

Range Hoods and Kitchen Ventilation

Gas ranges produce CO from incomplete combustion, particularly at low flame settings and on older unserviced burners, and measured rates vary widely with burner condition. The calculator's range preset is 50 mg/hr. At that rate, about 1.2 L/s of total ventilation holds CO at Health Canada's 10 ppm 24-hour limit with a 0.2 ppm background, so the concern is a small, tightly closed kitchen with several burners running: four burners at the preset in a 48 m3 kitchen at 0.2 ACH settle near 18 ppm. The kitchen exhaust calculator sizes the exhaust airflow for the cooking side, and this calculator shows whether that airflow also covers CO. See the CO2 level calculator for kitchen CO2 accumulation from gas combustion alongside CO.

Portable Generators

Portable generators are a major CO hazard during power outages. The CPSC staff briefing on generator CO emissions reports that a typical engine powering a 5 kW generator emits a weighted average of about 1,500 g/hr of CO, roughly the output of 450 idling cars, and counts 659 generator-related CO deaths in the US from 2004 to 2012. The calculator's generator preset uses that 1,500 g/hr figure, and it passes the 70 ppm alarm level in well under 15 minutes in a closed garage. Health Canada says never to run a generator indoors, in a garage, or in a shed, to operate it at least 6 metres (20 feet) from buildings with the exhaust pointed away from doors and windows, and to keep CO alarms working while it runs. During extended winter outages the temptation to move a generator indoors for warmth creates a serious risk.

Frequently Asked Questions

Health Canada's residential indoor air quality guideline limits indoor CO to 10 ppm (11.5 mg/m3) averaged over 24 hours and 25 ppm (28.6 mg/m3) over 1 hour. CO alarms certified to CSA 6.19 are built to sound at 70 ppm sustained for 60 to 240 minutes, so they don't trigger at the guideline levels, which is why ventilation and source control matter more than alarm placement alone. See the combustion air calculator for combustion appliance makeup air sizing.

The main CO sources are gas furnaces with cracked heat exchangers or blocked flues, gas water heaters, gas fireplaces, attached garages with idling vehicles, portable generators run near air intakes, gas ranges, and wood-burning appliances with incomplete combustion. Furnace heat exchanger failures are especially dangerous because the furnace can distribute combustion gases through the building. Attached garages are a significant source in cold climates where vehicles idle to warm up in winter.

Required total ventilation equals the CO emission rate divided by the allowable concentration above background, after converting units at 1.165 mg/m3 per ppm. For a gas range producing 50 mg/hr, holding CO at Health Canada's 10 ppm 24-hour limit takes about 1.2 L/s of total ventilation with a 0.2 ppm background. For a furnace leak at 500 mg/hr the same target takes about 12 L/s. Dilution can hold a steady-state number, but it is not a fix for a leaking furnace: the source has to be repaired. Use this calculator to see when ventilation is a viable control and when source remediation is required.

In a leaky older home at 0.5 ACH or higher, CO from a source dissipates quickly through natural infiltration. In the calculator's 173 m3 example, the 500 mg/hr furnace-leak preset settles near 5 ppm at 0.5 ACH but near 25 ppm at 0.1 ACH, above Health Canada's 10 ppm 24-hour limit. That is why Health Canada advises a CO alarm wherever combustion appliances are used, and why HVAC professionals doing air sealing work should verify CO alarm installation and check combustion appliances before tightening the building envelope. See the pollutant concentration calculator for general pollutant buildup modeling.